H07RN-F heavy-duty rubber-sheathed flexible cables are suitable for use under medium mechanical stress in dry, damp and wet areas, as well as outdoors and in agricultural installations.
This type of cable is suitable for equipment used in commercial operations, such as heating plates, hand lamps, and power tools such as drills or circular saws. It is also suitable for fixed installations on plaster and in temporary structures.
When installed in conduits or similar closed systems, it may be used at voltages of up to 1000 V AC (alternating current) or up to 750 V DC (direct current) to earth.
TECHNICAL DATA
General Description
Rubber connection cable, H07RN-F according to DIN VDE 0285-525-2-21 / DIN EN 50525-2-21; 07RN-F in accordance with DIN VDE 0285-525-2-21 / DIN EN 50525-2-21.
Temperature Range:
- Flexible installation: -25°C to +60°C
- Fixed installation: -30°C to +60°C
Permissible Operating Conductor Temperature: +60°C
Rated Voltage: AC U₀/U 450/750 V
Maximum Permissible Operating Voltage:
- Alternating current (AC), conductor-to-earth: 476 V
- Three-phase alternating current (AC), conductor-to-conductor: 825 V
- Direct current (DC), conductor-to-earth: 619 V
- Direct current (DC), conductor-to-conductor: 1238 V
Test Voltage Between Conductors: 2500 V
Tensile Stress:
During installation and operation: 15 N/mm²
Minimum Bending Radius:
- Fixed installation: 4 × outer diameter
- Flexible installation, guided by rollers: 7.5 × outer diameter
- Flexible installation, reeled on a drum: 5 × outer diameter
CERTIFICATIONS AND APPROVALS
- H07RN-F: HAR
- EAC
TECHNICAL DATA SHEET
If desired, you can download the technical data sheet
HERE.
CABLE CONSTRUCTION
- Bare copper conductor, finely stranded according to DIN VDE 0295 Class 5 / IEC 60228 Class 5
- Core insulation: rubber according to DIN VDE 0207-363-1 / DIN EN 50363-1 (EI4 compound type)
- Core identification according to DIN VDE 0293-308:
- 1 core: black
- 2 to 5 cores: colour-coded
- 7 to 37 cores: black cores with consecutive white numbering
- Protective conductor: from 3 cores onwards
- G = with green-yellow protective conductor in the outer layer
- x = without protective conductor
- Cores stranded in layers with optimized lay lengths
- Outer sheath: rubber according to DIN VDE 0207-363-2-1 / DIN EN 50363-2-1 (EM2 compound type)
- Sheath colour: black
PROPERTIES
- Resistant to oils and weathering effects
- Suitable for outdoor use
TESTS
- Flame-retardant according to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
- Oil-resistant according to DIN VDE 0473-811-404 / DIN EN 60811-404 / IEC 60811-404
NOTE
The conductor is manufactured in metric sizes (mm²). AWG sizes are approximate and are provided for reference purposes only.